29 CFR 1910.37

OSHA 1910.37 Exit Route Requirements

Officially titled Maintenance, safeguards, and operational features for exit routes. in 29 CFR 1910.37.

By ShieldSphere. Updated .

Short answer

OSHA 1910.37 requires employers to keep exit routes free and unobstructed, free of explosive or highly flammable decorations, and arranged so employees do not travel toward a high hazard area unless the path is effectively shielded. Exits must be marked by illuminated Exit signs, routes must be adequately lighted, emergency safeguards must work at all times, and an operable employee alarm system is required unless employees can promptly see or smell the hazard in time.

What 1910.37 requires

The standard covers how an exit route is kept usable day to day, not how it is first designed. It has five parts: hazard control along the route, lighting and marking, fire retardant finishes, protection during construction or alterations, and an employee alarm system.

Keeping the route clear and away from hazards

Exit routes must be kept free of explosive or highly flammable furnishings or other decorations under 1910.37(a)(1). Under 1910.37(a)(2), routes must be arranged so employees do not have to travel toward a high hazard area, unless the path of travel is effectively shielded from it by suitable partitions or other physical barriers. Exit routes must be free and unobstructed, and no materials or equipment may be placed in the route, either permanently or temporarily, per 1910.37(a)(3). That same paragraph bars an exit access that goes through a room that can be locked, such as a bathroom, or that leads into a dead-end corridor. It also requires stairs or a ramp where the exit route is not substantially level, 1910.37(a)(3).

Safeguards designed to protect employees during an emergency, such as sprinkler systems, alarm systems, fire doors and exit lighting, must be in proper working order at all times under 1910.37(a)(4).

Lighting, exit signs and directional signs

  • Each exit route must be adequately lighted so that an employee with normal vision can see along it, 1910.37(b)(1).
  • Each exit must be clearly visible and marked by a sign reading Exit, 1910.37(b)(2).
  • Each exit route door must be free of decorations or signs that obscure its visibility, 1910.37(b)(3).
  • Where the direction of travel to the exit or exit discharge is not immediately apparent, signs along the exit access must show the direction to the nearest exit and exit discharge, and the line of sight to an exit sign must be clearly visible at all times, 1910.37(b)(4).
  • Each doorway or passage that could be mistaken for an exit must be marked Not an Exit or a similar designation, or be identified by a sign showing its actual use, 1910.37(b)(5).
  • Each exit sign must be illuminated to a surface value of at least five foot-candles by a reliable light source and be distinctive in color, though self-luminous or electroluminescent signs with a minimum luminance surface value of at least .06 footlamberts are permitted, 1910.37(b)(6).
  • The word Exit must be in plainly legible letters not less than six inches high, with principal strokes not less than three-fourths of an inch wide, 1910.37(b)(7).

Fire retardant finishes

Where fire retardant paints or solutions are used, they must be renewed as often as necessary to maintain their fire retardant properties, 1910.37(c).

Construction, repairs and alterations

During new construction, employees must not occupy a workplace until the required exit routes are completed and ready for use for the portion they occupy, 1910.37(d)(1). During repairs or alterations, employees must not occupy the workplace unless the required exit routes are available and existing fire protections are maintained, or until alternate fire protection providing an equivalent level of safety is furnished, 1910.37(d)(2). Under 1910.37(d)(3), employees must not be exposed to hazards of flammable or explosive substances or equipment used during the work that are beyond the normal permissible conditions in the workplace, or that would impede exiting.

Employee alarm system

Employers must install and maintain an operable employee alarm system with a distinctive signal to warn employees of fire or other emergencies, unless employees can promptly see or smell a fire or other hazard in time to provide adequate warning, 1910.37(e). The alarm system must comply with 1910.165, 1910.37(e).

Who 1910.37 applies to

The section applies to general industry workplaces where employees use exit routes, which in practice means nearly every building or structure where people work. Its duties are framed around protecting employees: 1910.37(a)(1) opens with the requirement that the danger to employees must be minimized, and 1910.37(b)(1) sets the lighting test by what an employee with normal vision can see.

The duties attach to the route itself and to everything along it. That includes the exit access leading to an exit, the exit, and the exit discharge, which is why 1910.37(b)(4) speaks of signs posted along the exit access pointing to the nearest exit and exit discharge. Doorways and passages that are not exits are also covered, because 1910.37(b)(5) requires those that could be mistaken for an exit to be marked.

The section reaches beyond normal operations. Workplaces under new construction are covered by 1910.37(d)(1), and occupied facilities undergoing repairs or alterations are covered by 1910.37(d)(2) and 1910.37(d)(3). Emergency equipment such as sprinklers, alarms, fire doors and exit lighting falls under 1910.37(a)(4), and the alarm system itself under 1910.37(e).

What a compliant exit route maintenance program looks like

The standard does not require a written exit route program, but its duties are continuous, so most employers handle them through routine inspections and clear ownership. The following practices are common ways to meet the rule rather than requirements stated in it.

  • A floor plan that marks every exit route, exit, exit discharge and Not an Exit door, so inspectors and supervisors check the same paths.
  • A short walk-through checklist covering obstructions, locked or blocked doors, lighting, sign illumination, sign visibility, and decorations near exit doors.
  • A named owner for each area, typically a supervisor or facilities lead, who corrects blocked routes on the spot rather than logging them for later.
  • Inspection and testing records for sprinklers, fire doors, emergency lighting, exit sign lamps and batteries, and the alarm system, kept with service contractor reports.
  • A change review step for layout changes, new racking, seasonal decorations and events, so a new arrangement is checked against exit routes before it goes in.
  • A pre-construction checklist for renovations that confirms which routes stay open, how existing fire protection is maintained or replaced, and where flammable materials will be stored.
  • Training that tells employees how the alarm sounds, where the nearest exits are, and that placing anything in an exit route is not allowed.

Tie these routines to your emergency action plan and fire prevention plan so that evacuation procedures, alarm signals and housekeeping duties match the routes you actually maintain.

Common exit route mistakes and frequently cited problems

  • Temporary storage in the route. Pallets, carts or boxes left for an hour still violate the rule, because 1910.37(a)(3) bars materials and equipment placed permanently or temporarily.
  • Locked or chained exit doors, or an exit access that passes through a lockable room such as a restroom or office, which 1910.37(a)(3) prohibits.
  • Dead-end corridors created when racking, partitions or new rooms are added without checking the exit path, also barred by 1910.37(a)(3).
  • Burned-out exit sign lamps, dead backup batteries, or signs hidden behind hanging stock and banners, which conflict with 1910.37(b)(4) and 1910.37(b)(6).
  • Missing directional signs in large warehouses or plants where the way out is not obvious from the work area, 1910.37(b)(4).
  • Storage room or closet doors that look like exits but carry no Not an Exit or actual-use sign, 1910.37(b)(5).
  • Holiday decorations or posters covering exit doors, 1910.37(b)(3).
  • Fire doors propped open or sprinkler and alarm components left impaired after maintenance, which conflicts with the working-order duty in 1910.37(a)(4).
  • Keeping employees in a building under renovation while contractors block exits or disable fire protection without an equivalent alternative, 1910.37(d)(2).

Most of these problems come from treating exit routes as a one-time design feature. The rule is about ongoing maintenance, so the routes drift out of compliance whenever housekeeping, layout or maintenance slips.

Regulatory text

Short excerpts quoted exactly from 29 CFR 1910.37 as published in the eCFR. Read the full section for everything it requires.

1910.37(a)(3)

This is the core housekeeping duty and the one most often found broken during walk-throughs.

(3) Exit routes must be free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, nor may it lead into a dead-end corridor.
1910.37(a)(4)

Emergency equipment has to work every day, not just when it is tested.

(4) Safeguards designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting) must be in proper working order at all times.
1910.37(b)(6)

These are the measurable performance criteria for exit sign illumination.

(6) Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m 2) are permitted.
1910.37(d)(2)

Renovations in occupied buildings must keep exits available and fire protection intact or replaced.

(2) During repairs or alterations, employees must not occupy a workplace unless the exit routes required by this subpart are available and existing fire protections are maintained, or until alternate fire protection is furnished that provides an equivalent level of safety.
1910.37(e)

This sets the alarm duty and its single condition for when an alarm is not needed.

Employers must install and maintain an operable employee alarm system that has a distinctive signal to warn employees of fire or other emergencies, unless employees can promptly see or smell a fire or other hazard in time to provide adequate warning to them.

Frequently asked questions

Can materials be stored in an exit route temporarily under OSHA 1910.37?

No. Under 1910.37(a)(3), exit routes must be free and unobstructed, and no materials or equipment may be placed within the exit route either permanently or temporarily. A pallet staged for a short delivery window or a cart parked in a corridor still counts.

How bright does an exit sign have to be under 1910.37?

Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color, 1910.37(b)(6). Self-luminous or electroluminescent signs are permitted if they have a minimum luminance surface value of at least .06 footlamberts. The lettering must read Exit in plainly legible letters not less than six inches high with principal strokes at least three-fourths of an inch wide, 1910.37(b)(7).

When does a door need a Not an Exit sign?

Under 1910.37(b)(5), each doorway or passage along an exit access that could be mistaken for an exit must be marked Not an Exit or a similar designation, or be identified by a sign indicating its actual use, such as closet. A door that leads to a storage room, mechanical room or stairway to a basement is a typical example.

Can an exit route pass through a restroom or office?

Not if the room can be locked. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, and it may not lead into a dead-end corridor, 1910.37(a)(3).

Is an employee alarm system always required by 1910.37?

Employers must install and maintain an operable employee alarm system with a distinctive signal to warn employees of fire or other emergencies, unless employees can promptly see or smell a fire or other hazard in time to provide adequate warning, 1910.37(e). That condition fits small, open spaces where everyone would notice a fire right away. Where an alarm is used, it must comply with 1910.165, 1910.37(e).

Can employees work in a building during renovation under 1910.37?

Yes, with conditions. During repairs or alterations, employees must not occupy a workplace unless the required exit routes are available and existing fire protections are maintained, or until alternate fire protection with an equivalent level of safety is furnished, 1910.37(d)(2). Employees also must not be exposed to flammable or explosive hazards from the work that exceed normal permissible conditions or would impede exiting, 1910.37(d)(3).

Key takeaways

  • Nothing may be placed in an exit route, even temporarily, and routes cannot pass through lockable rooms or end in dead ends.
  • Every exit needs a visible, illuminated Exit sign with letters at least six inches high, plus directional signs where the way out is not obvious.
  • Doors that could be mistaken for exits must be marked Not an Exit or labeled with their actual use.
  • Sprinklers, alarms, fire doors and exit lighting must be in proper working order at all times.
  • During renovations, keep exits available and fire protection maintained, or provide an equivalent alternative.
  • An operable alarm with a distinctive signal is required unless employees can promptly see or smell the hazard in time.

Sources

Find hazards before an inspector does

Upload a photo of your workplace and the AI Hazard Scanner flags visible hazards against the OSHA standards that apply to your site. Your first scan is free, no account required.

Find hazards before an inspector does

Last reviewed against the eCFR on November 10, 2026.

How these pages are produced and checked

This page is educational information about OSHA requirements and is not legal advice. Regulatory text is quoted from the Code of Federal Regulations and may have been amended since this page was last reviewed. Confirm how 29 CFR 1910.37 applies to your workplace with a qualified safety professional.